Product
Product Features
PROFINET® IO Module
Connection to a PROFINET® network
PROFINET® IO Controller module specifications
| Item | RJ71PN92 |
|---|---|
| Data exchange | |
| Max. input data length per network (word) | 4096 |
| Max. output data length per network (word) | 4096 |
| Max. input data length per IO device (byte) | 1437 |
| Max. output data length per IO device (byte) | 1437 |
| Cycle time (ms) | 512 (max.), 1 (min.)*1 |
| Service interface | |
| Maximum transmission capacity per request (byte) | 4116 |
| Maximum number of connectable IO devices | 128 |
| Data transmission speed*2 (bps) | 1G/100M/10M |
*1: The cycle time depends on the number of IO devices and the input/output data length.
*2: Data communications at 100 Mbps is recommended.
*2: Data communications at 100 Mbps is recommended.
PROFINET® IO Device module specifications
| Item | RJ71PN93 |
|---|---|
| Data exchange | |
| Max. I/O data length (byte) | 1024 (Total size of the I/O data)*3 |
| Cycle time (ms) | 512 (max.), 2 (min.) |
| Other | |
| PROFINET communication specifications | Conformance Class B |
| MRP (Media redundancy protocol) | MRC*4 |
| Data transmission speed*2 (bps) | 100M/10M |
*4: The RJ71PN93 operates as an MRC in a ring topology. To perform communications in the ring topology, a device in the ring topology has to operate as the MRM (Media redundancy manager).