Product
Product Features
Multiple Input (Voltage/Current/Temperature) Module
Channel isolated multiple input
L60MD4-GNumber of inputs: 4 channels
Input voltage: -10 to 10 V DC
Input current: 0 to 20 mA DC
Input micro voltage: -100 to 100 mV
Input thermocouple: K, J, T, E, N, R, S, B, U, L, PLⅡ, W5Re/W26Re
Input RTD: Pt1000, Pt100, JPt100, Pt50
Conversion speed: 50 ms/channel
Resolution
Voltage/Current/micro voltage: 1/20000Thermocouple: B, R, S, N, PLⅡ, W5Re/W26Re: 0.3℃, K, E, J, T, U, L: 0.1℃RTD: Pt100, JPt100: 0.03℃/0.1℃, Pt1000, Pt50: 0.1℃
Input voltage: -10 to 10 V DC
Input current: 0 to 20 mA DC
Input micro voltage: -100 to 100 mV
Input thermocouple: K, J, T, E, N, R, S, B, U, L, PLⅡ, W5Re/W26Re
Input RTD: Pt1000, Pt100, JPt100, Pt50
Conversion speed: 50 ms/channel
Resolution
Voltage/Current/micro voltage: 1/20000Thermocouple: B, R, S, N, PLⅡ, W5Re/W26Re: 0.3℃, K, E, J, T, U, L: 0.1℃RTD: Pt100, JPt100: 0.03℃/0.1℃, Pt1000, Pt50: 0.1℃
Analog Input Modules
Analog Input
L60AD4Number of inputs: 4 channels
Input voltage: -10 to 10 V DC
Input current: 0 to 20 mA DC
Conversion speed: 20 μs/channel
Resolution: 1/20000
Input voltage: -10 to 10 V DC
Input current: 0 to 20 mA DC
Conversion speed: 20 μs/channel
Resolution: 1/20000
Analog Input
L60ADVL8Number of inputs: 8 channels
Input voltage: -10 to 10 V DC
Conversion speed: 1 ms/channel
Resolution: 1/16000
Input voltage: -10 to 10 V DC
Conversion speed: 1 ms/channel
Resolution: 1/16000
Analog Input
L60ADIL8Number of inputs: 8 channels
Input current: 0 to 20 mA DC
Conversion speed: 1 ms/channel
Resolution: 1/8000
Input current: 0 to 20 mA DC
Conversion speed: 1 ms/channel
Resolution: 1/8000
Analog Output Modules
Analog Output
L60DA4Number of outputs: 4 channels
Output voltage: -10 to 10 V DC
Output current: 0 to 20 mA DC
Conversion speed: 20 μs/channel
Resolution: 1/20000
Output voltage: -10 to 10 V DC
Output current: 0 to 20 mA DC
Conversion speed: 20 μs/channel
Resolution: 1/20000
L60DAVL8Number of outputs: 8 channels
Output voltage: -10 to 10 V DC
Conversion speed: 200 μs/channel
Resolution: 1/16000
Output voltage: -10 to 10 V DC
Conversion speed: 200 μs/channel
Resolution: 1/16000
L60DAIL8Number of outputs: 8 channels
Output voltage: 0 to 20 mA DC
Conversion speed: 200 μs/channel
Resolution: 1/8000
Output voltage: 0 to 20 mA DC
Conversion speed: 200 μs/channel
Resolution: 1/8000
Analog I/O Module
Analog I/O
L60AD2DA2Analog input specifications
Number of inputs: 2 channels
Input voltage: -10 to 10 V DC
Input current: 0 to 20 mA DC
Conversion speed: 80 μs/channel
Resolution: 1/12000Analog output specifications
Number of outputs: 2 channels
Output voltage: -10 to 10 V DC
Output current: 0 to 20 mA DC
Conversion speed: 80 μs/channel
Resolution: 1/12000
Number of inputs: 2 channels
Input voltage: -10 to 10 V DC
Input current: 0 to 20 mA DC
Conversion speed: 80 μs/channel
Resolution: 1/12000Analog output specifications
Number of outputs: 2 channels
Output voltage: -10 to 10 V DC
Output current: 0 to 20 mA DC
Conversion speed: 80 μs/channel
Resolution: 1/12000
Temperature Input Module
RTD input
L60RD8Number of inputs: 8 channels
Input RTD: Pt1000, Pt100 (JIS C 1604-2013), JPt100 (JIS C 1604-1981), Pt50 (JIS C 1604-1981), Ni500 (DIN 43760 1987), Ni120 (DIN 43760 1987), Ni100 (DIN 43760 1987), Cu100 (GOST 6651-2009, α=0.00428), Cu50 (GOST 6651-2009, α=0.00428)
Conversion speed: 40 ms/ch
Resolution: 0.1℃
Input RTD: Pt1000, Pt100 (JIS C 1604-2013), JPt100 (JIS C 1604-1981), Pt50 (JIS C 1604-1981), Ni500 (DIN 43760 1987), Ni120 (DIN 43760 1987), Ni100 (DIN 43760 1987), Cu100 (GOST 6651-2009, α=0.00428), Cu50 (GOST 6651-2009, α=0.00428)
Conversion speed: 40 ms/ch
Resolution: 0.1℃
■ Multiple/analog/temperature input features
Function | Multiple input (voltage/current/temperature) module | Analog input module | Analog I/O module | Temperature input module | ||||
---|---|---|---|---|---|---|---|---|
L60MD4-G | L60AD4 | L60ADVL8 | L60ADIL8 | L60AD2DA2 | L60RD8 | |||
Channel isolation | ● | — | — | — | — | — | ||
AD conversion method | Sampling processing | ● | ● | ● | ● | ● | ● | |
Averaging processing | Time average | ● | ● | ● | ● | ● | ● | |
Count average | ● | ● | ● | ● | ● | ● | ||
Moving average | ● | ● | ● | ● | ● | ● | ||
Time lag filter function | — | — | — | — | — | — | ||
Digital filtering function | — | — | — | — | — | — | ||
Conversion speed switch function | — | ● | — | — | — | — | ||
Input range extended mode function | ● | ●*1 | ● | ● | ● | — | ||
Maximum value/minimum value hold function | ● | ● | ● | ● | ● | ● | ||
Disconnection detection function | ● | — | — | — | — | ● | ||
Input signal error detection function | ● | ● | ● | ● | ● | — | ||
Input signal error detection extension function | — | ●*1 | ● | ● | — | — | ||
Warning output function | Process alarm | ● | ● | ● | ● | — | ● | |
Rate alarm | ● | — | — | — | — | ● | ||
Scaling function | ● | ● | ● | ● | ● | ● | ||
2-point sensor compensation function | — | — | — | — | — | ● | ||
Shift function | —*2 | ●*1 | —*2 | —*2 | —*2 | ● | ||
Digital clipping function | —*2 | ●*1 | —*2 | —*2 | —*2 | — | ||
Difference conversion function | —*2 | ●*1 | —*2 | —*2 | —*2 | — | ||
Logging function | —*3 | ●*1 | —*3 | —*3 | ● | —*3 | ||
Flow amount integration function | — | ●*1 | — | — | — | — | ||
Trigger conversion function | — | — | — | — | — | — | ||
Variable arithmetic function | — | — | — | — | ●*4 | — | ||
Variable conversion characteristics function | — | — | — | — | ●*4 | — | ||
Variable conversion characteristics function + variable arithmetic function | — | — | — | — | ●*4 | — |
Supported by models whose first five serial number digits are "13041" or later.
Please use function blocks (FB) for the shift function, digital clipping function, and difference conversion function. The function blocks (FB) can be downloaded for free from the MELSOFT Library on the Mitsubishi Electric FA site.
For logging, please use the data logging function of the CPU module.
Supported by models whose first five serial number digits are "17042" or later.
■ Analog output features
Function | Analog output module | Analog I/O module | |||
---|---|---|---|---|---|
L60DA4 | L60DAVL8 | L60DAIL8 | L60AD2DA2 | ||
Analog output HOLD/CLEAR function | ● | ● | ● | ● | |
Scaling function | ● | ● | ● | ● | |
Warning output function | Process alarm | ● | ● | ● | ● |
Wave output function | ●*5 | ● | ● | ● | |
Wave output step action function | ●*5 | ● | ● | ● | |
Variable arithmetic function | — | — | — | ●*6 | |
Variable conversion characteristics function | — | — | — | ●*6 | |
Variable conversion characteristics function + variable arithmetic function | — | — | — | ●*6 |
*5: Supported by models whose first five serial number digits are "14041" or later.
*6: Supported by models whose first five serial number digits are "17042" or later.
Temperature Control Modules
Thermocouple input
L60TCTT4Number of inputs: 4 channels
L60TCTT4BWNumber of inputs: 4 channels
Heater disconnection detection function
Heater disconnection detection function
RTD input
L60TCRT4Number of inputs: 4channels
L60TCRT4BWNumber of inputs: 4 channels
Heater disconnection detection function
Heater disconnection detection function
Function | L60TCTT4 | L60TCTT4BW | L60TCRT4 | L60TCRT4BW |
---|---|---|---|---|
Thermocouple input | RTD input | |||
Standard control | ● | ● | ● | ● |
Heating-cooling control | ● | ● | ● | ● |
Self-tuning function | ● | ● | ● | ● |
Peak current suppression function | ● | ● | ● | ● |
Simultaneous temperature rise function | ● | ● | ● | ● |
Selectable sampling cycle | ● | ● | ● | ● |
Temperature input mode | ● | ● | ● | ● |
Temperature control mode | ● | ● | ● | ● |